VAR95: Var Transducer
VAR95 "WISCO" Var Transducer
- oltage Input 110 VAC, 220 VAC, 380 VAC
- Current Input 1 A, 5 A
- Analog Output 4-20 mA, 0-5 VDC
Calibration var of rated output
| Connection | V=110V | V=220V | V=380V | ||||||
|
|
|
|||||||
| Single Phase |
|
|
|
||||||
| 3phase,3wire |
|
|
|
||||||
| 3phase,4wire |
|
|
|
Note. V= Line voltage
Equation to calculated measuring range
Measuring range = Calibration var x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W
Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.
The Var Transducers VAR95 are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.
Specifications
|
Input |
||||
| Number of channel |
: | 3 Channel |
||
| Input type |
: | Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire) |
||
| Input range |
: | Current (1, 5 A AC) |
||
| : | Voltage (110, 220, 380 VAC (Line voltage for 3 phase) |
|||
| Power consumption |
: |
< 0.2 VA for input current, < 0.4 VA for voltage input
|
||
| Frequency |
: | 50 Hz. |
||
|
Analog Output |
||||
| Number of Channel |
: | 1 Channel |
||
| Output Type |
: | Current, Voltage |
||
| Output Range |
: | Current Max (-)1 to 1 mA (Load Resistance 10 KΩ) |
||
| Current Max 4 to 20 mA (Load Resistance 600 Ω) |
||||
| Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω) |
||||
| Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω) |
||||
| Voltage Min 0 to 1 VDC (Load Resistance 500 Ω) |
||||
| Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ) |
||||
| Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ) |
||||
| Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ) |
||||
| Linearity |
: |
< ¾ 0.5% of span
|
||
|
Power Requirements |
||||
| Power Supply |
: | 110, 220 VAC |
||
|
Environmental Limits |
||||
| Operating Temperature |
: | 0 to 55 °C |
||
| Operating Humidity |
: | 5 to 95 %RH |
||
| Storage Temperature |
: | 0 to 70 °C |
||
|
Physical Characteristics |
||||
| Dimension |
: | W132 x H132 x D162 mm. |
||
| Mounting |
: | Wall Mount |
||
| Wiring |
: |
Screw Terminals
|
||
|
Warranty |
||||
| Warranty Period |
: | 5 Year |
Contact Us
KDN AUTOMATION AND SERVICE CO.,LTD.
Tel : 02-023-3038, 082-550-3096
Line official : kdnautomation
E-mail: kdnautomation@gmail.com