WAT95: Watt Transducer

WAT95 "WISCO" Watt Transducer

  • High accuracy
  • Long term stability
  • Time-Division Multiplication principle

 

 

 

Calibration watt of rated output

Connection

V=110V

V=220V

V=380V

 

I=1A

I=5A

I=1A

I=5A

I=1A

I=5A

Single Phase

100W

500W

200W

1000W

-

-

3phase,3wire

200W

1000W

400W

2000W

600W

3000W

3phase,4wire

200W

1000W

400W

2000W

600W

3000W

Note. V= Line voltage

Equation to calculated measuring range
Measuring range = Calibration watt x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration watt = 1000W
Measuring range = 1000 x 220/110 x 250/5 = 100 KW.

 

 

            Watt Transducers WAT95 are used to convert single or three phaseunbalance load active power into a proportional load independent DC. Output. Based fully on electronic Time-Division Multiplication measuring principle, the true power of a network with any power factor range are linearly produced by Watt Transducer output.

 

 

Specifications

 

Input

       
Number of channel

  :   3 Channel

Input type

  :   Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire)
Input range

  :   Current (1, 5 A), Accuracy Class: 0.5

    :   Voltage (110, 220, 380 VAC (Line voltage for 3 phase)

Power Consumption
    < 0.2 VA for input current, < 0.4 VA for voltage input
Frequency
  :  
50 Hz.

 

Analog Output

       
Number of Channel
  :   1 Channel
Output Type
  :   Current, Voltage
Output Range
  :   Current Max 0 to 1 mA (Load Resistance 10 KΩ)

        Current Max 4 to 20 mA (Load Resistance 600 Ω)
        Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω)
        Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω)
        Voltage Min 0 to 1 VDC (Load Resistance 500 Ω)
        Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ)
        Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ)
        Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ)
Linearity
  :   < ± 0.5 % of span

  

Power Requirements

       
Power Supply
  :   110, 220 VAC

 

 

       
Operating Temperature

  :   0 to 55 °C
Operating Humidity
    5 to 95 %RH
Storage Temperature
  :   0 to 70 °C

 

Physical Characteristics

       
Dimension
  :   W132 x H132 x D162 mm.
Mounting

  :   Wall Mount
Wiring

  :  
Screw Terminals

Protection
  :    IP20

 

Warranty

       
Warranty Period
    5 Year

 

 

 

Contact Us

KDN AUTOMATION AND SERVICE CO.,LTD. 

Tel : 02-023-3038, 082-550-3096

​Line official : ​​kdnautomation

E-mail: kdnautomation@gmail.com