VT95: Voltage Transducer

VT95 "WISCO" Voltage Transducer

  • Voltage Input 0-150 VAC, 0-300 VAC
  • Analog Output 4-20 mA, 0-5 VDC, 0-10 VDC

     

 

            Voltage Transducer VT95 is designed for converting sinusoidal alternating voltage into a load dependent DC output signal proportional to the measured RMS input values.

 


Specifications



Input

       
Number of channel

  :   1 Channel

Input type

  :   Voltage
Input range

  :   0 to 150, 0 to 300 VAC

    :   (Overange 120% continuously, 150% for 10 sec)

Input loss

  :  
< 0.3 VA

 

Analog Output

       
Number of Channel
  :   1 Channel
Output Type
  :   Current, Voltage
Output Range
  :   Current Max 0 to 1 mA (Load Resistance 10 KΩ)
        Current Max 0 to 5 mA (Load Resistance 2 KΩ)
        Current Max 0 to 10 mA (Load Resistance 1 KΩ)
        Current Max 0 to 20 mA (Load Resistance 600 Ω)
        Current Max 4 to 20 mA (Load Resistance 600 Ω)

        Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω)

        Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω)

        Voltage Min 0 to 1 VDC (Load Resistance 500 Ω)

        Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ)
        Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ)
        Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ)
Linearity
  :   < ± 0.5 % of span

  

Power Requirements

       
Power Supply
  :   110, 220 VAC

 

Environmental Limits

       
Operating Temperature

  :   0 to 55 °C
Operating Humidity
    5 to 95 %RH
Storage Temperature
  :   0 to 70 °C

 

Physical Characteristics

       
Dimension
  :   W50 x H70 x D130 mm.
Mounting

  :   Wall or DIN rail
Connection
  :   plug - in Wiring Screw terminals on base socket

 

Warranty

       
Warranty Period
    5 Year

 

 

  

Contact Us

KDN AUTOMATION AND SERVICE CO.,LTD. 

Tel : 02-023-3038, 082-550-3096

​Line official : ​​kdnautomation

E-mail: kdnautomation@gmail.com

Visitors: 112,157