RT95: RTD Transmitter

RT95 "WISCO" RTD Transmitter

  • Linearizing for Pt100 sensor
  • Programmable range
  • Isolated input to output to Power Supply.
  • True lead length compensation

 

 

 

 

 

 

 

               RTD Transmitter RT95 are compactly designed for converting the variations of resistance in a Pt100 temperature sensor to a linearized and isolated DC. voltage or current output. They provide constant current excitation and true lead length compensation when used with a 3-wire RTD, which can be located at a considerable distance from the transmitter.

 

    

 

 

Specifications

 

RTD Input

       
Number of channel

  :   1 Channel

Input type

  :   Pt100 DIN or JIS (3 Wire Connection)
Input range

  :   Rangeable zero from - 100 °C to +100 °C
        Rangeable span from 15 °C to 500 °C

        Other types of RTD input available Cu 100, Pt 1000

Input impedance
    Lead wire resistance 5 ohm/wire max.

 

Analog Output

        
Number of Channel
  :   1 Channels

Output type

    Current, Voltage

Output range
  :   Current (4 to 20 mA)

        Voltage (0 to 5, 1 to 5, 0 to 10 VDC)

Linearity
  :   < ± 0.2% of span
Output Load Resistance

  :   Current: Max. 1000 Ω Load

        Voltage (min 1000 Ω load)

Isolation Voltage
  :  
500 VAC (1 min.) between input, output, power supply (1min. test)

  

Power Requirements

       
Power Supply
  :   100,110, 220 VAC

       
24 VDC (Optional)

 

Environmental Limits

       
Operating Temperature

  :   0 to 55 °C 
Operating Humidity
   
5 to 95 %RH

Storage Temperature
  :   0 to 70 °C

 

Physical Characteristics

       
Dimension
  :   W50 x H70 x D130 mm.

Mounting

  :   Wall or DIN rail

Connection
  :   Plug-in 11 pins socket

 

Warranty

       
Warranty Period
    5 Year

 

 

Contact Us

KDN AUTOMATION AND SERVICE CO.,LTD. 

Tel : 02-023-3038, 082-550-3096

​Line official : ​​kdnautomation

E-mail: kdnautomation@gmail.com