Acuvim-CL-D-5A-P1 Power Meter

 

Acuvim-CL-D-5A-P1 Power Meter

Model: Acuvim-CL-D-5A-P1

  • เครื่องวัดพลังงาน Acuvim-CL พร้อมเอาต์พุต MODBUS RS485
  • พร้อมจอแสดงผล LCD บนตัวบอร์ดอินพุต 5A
  • สำหรับหม้อแปลงกระแสไฟฟ้าและอินพุทแหล่งจ่ายไฟ AC ขนาดกว้าง

 

 

           About the Acuvim-CL
             A highly capable but lower cost series of multi-functional single/three phase MODBUS RS485 power meters that measures most common electrical parameters. Available with LCD display or DIN Rail mount transducer (no display). All versions include MODBUS RS485 output.

Key Features

Metering

  • Voltage V1, V2, V3, V12, V23, V31
  • Current I1, I2, I3, In
  • Power P1, P2, P3, Psum
  • Reactive Power Q1, Q2, Q3, Qsum
  • Apparent Power S1, S2, S3, Ssum
  • Frequency F
  • Power Factor PF1, PF2, PF3, PF
  • Energy Ep_imp, Ep_exp
  • Reactive Energy Eq_imp, Eq_exp
  • Apparent Energy Es
  • Demand Dmd_I1, Dmd_I2, Dmd_I3, Dmd_P, Dmd_Q, Dmd_S

Monitoring

  • Power Quality (functions not included with the Acuvim-KL)
  • Voltage Harmonics 2nd to 15th and THD( Acuvim-DL is from 2nd to 25th)
  • Current Harmonics 2nd to 15th and THD( Acuvim-DL is from 2nd to 25th)
  • Voltage Unbalance Factor U_unbl (all models excluding the Acuvim-KL)
  • Current Unbalance Factor I_unbl (all models excluding the Acuvim-KL)
  • Max/Min Statistics (all models excluding the Acuvim-KL)
  • Meter Running Time and Load Running Time (Acuvim-DL/EL/KL)

Alarms

         Two (2) parameters may be set within a specified time interval. If indicated parameter is over or under its setting limit and persists over the specified time interval, 

the event will be recorded with time stamps and trigger the alarm DO output. The indicated parameter can be selected from any of the 35 parameters available.

Communication

           RS485, industry standard Modbus® RTU protocol; (Only on models CL/DL/EL/KL)
Option the second RS485, Modbus® RTU protocol; or PROFIBUS-DP/V0 (available for the DL/EL Models) 
Protocol. (just for Acuvim-DL/EL)

Display

           Clear and large character LCD Screen display with white back light; Wide environmental temperature endurance.

Acuview Software

          As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.

Acuview Software Features

  • Simple setup feature for fast deployment and configuration Accuenergy meters.
  • Remote and real time monitoring of all meter parameters.
  • Dozens of meters can be connected to a single PC.
  • Multiple meters can be displayed and tiled in one window.
  • Real Time Data Logging.
  • Logging of data from the I/O modules (pulses from Water, gas, flow, etc).
  • All data logged into simple and easy to read Excel spreadsheets (.xls, .csv or .txt formats).
  • SmartSum feature provides aggregate Energy & Demand data for an average of the entire system being monitored.

 

Applications

  • Metering of distribution feeders, transformers, generators, capacitor banks and motors.
  • Medium and low voltage systems.
  • Commercial, industrial, utility.
  • Power quality analysis.

 

Specifications        
Metering        
Parameters Acuvim-L Accuracy Acuvim-EL/KL Accuracy Resolution Range
Voltage 0.50% 0.50% 0.1V 20V~1000kV
Current 0.50% 0.50% 0.001A 0~50000A
Current Demand 0.50% 0.50% 0.001A 0~50000A
Power 1.00% 0.50% 1W -9999MW~9999MW
Reactive Power 2.00% 0.50% 1var -9999Mvar~9999Mvar
Apparent Power 1.00% 0.50% 0.001V 0~9999MVA
Power Demand 1.00% 0.50% 1W -9999MW~9999MW
Reactive Power Demand 2.00% 0.50% 1var -9999Mvar~9999Mvar
Apparent Power Demand 1.00% 1VA 1VA 0~9999MVA
Power Factor 1.00% 0.50% 0.001 -1.0~1.0
Frequency 0.20% 0.20% 0.01Hz 45.00~65.00Hz
Energy 0.50% 0.50% 0.1kWh 0~99999999.9kWh
Reactive Energy 2.00% 0.50% 0.1kvarh 0~99999999.9kvarh
Apparent Energy 1.00% 0.50% 0.1VAh 0~99999999.9kVAh
Harmonics 2.00% - 0.01% 0~100.0%
Running Time     0.1hrs 0~999999999.9hrs
Communication        
RS-485 (Option)        
Modbus-RTU Protocol        
2-wire connection, Half-duplex, Isolated        
1200 to 38400 baud rate        
Input        
Current Inputs (Each Channel)        
Nominal Current 5 A ac      
Metering Range 0~6 A ac      
Withstand 20Arms continuous100Arms for 1 second, non-recurring    
Burden 0.05VA (typical) @5Arms      
Pickup Current 10Vac      
Accuracy 0.50%      

Voltage Inputs

(Each Channel)

       
Nominal Full Scale 400Vac L-N, 690Vac L-L (+20%)      
Withstand 1500Vac continuous2500Vac, 50/60Hz for 1minute      
Input Impedance 45Hz~65Hz      
Pickup Voltage 10Vac      
Accuracy 0.50%      
Energy Accuracy (Acuvim-EL)        
Active (according to IEC 62053-22) Class 0.5s(according to ANSI C12.20) Class 0.5    
Reactive (according to IEC 62053-23) Class 2      
Harmonic Resolution        
Metered Value 2nd ~ 15th harmonics(THD of Acuvim-DL is 2nd to 25th)      
Control Power        
Universal AC or DC      
AC/DC Control Power        
Operating Range 100~415Vac, 50/60Hz, 100~300Vdc      
Burden 3W      
Withstand 3250Vac, 50/60Hz for 1 minute      
Low Voltage DC Control Power (Optional)        
Operating Range 20~60Vdx      
Burden 3W      
Digital Output Option        
Digital Output (DO) (Photo-MOS)      
Voltage Range 0~250Vac/dc      
Load Current 100mA (Max)      
Output Frequency 25Hz, 50% Duty Ratio      
Isolation Voltage 2500V      
Digital Input Option        
Digital Output (DI)        
Input Voltage Range 20~250Vac/dc      
Input Current (Max) 2mA      
Start Voltage 15V      
Stop Voltage 5V      
Pulse Frequency (Max) 100Hz, 50% Duty Ratio      
SOE Resolution 2ms      
Operating Environment        
Operation Temperature -25°C to 70°C      
Storage Temperature -40°C to 85°C      
Relative Humidity 5% to 95% non-condensing      
Pollution Degree 2      
Standard Compliance        
Product        
USA UL 61010-1      
Canada cUL 61010-1      
Europe IEC 61010-1      
Emission        
Radiated/Conducted FCC Part 15 Subpart B, Class A      
Radiated/Conducted EN 55011      
Harmonic IEC 61000-3-2      
Voltage Fluctuation IEC 50081-2      
Radio Interference IEC 50081-2      
Immunity        
ESD IEC 61000-4-2      
Radiated, radio-frequency, electromagnetic field IEC 61000-4-3      
Electrical fast transient/bust IEC 61000-4-4      
Surge IEC 61000-4-5      
Conducted disturbances IEC 61000-4-6      
Power frequency magnetic field IEC 61000-4-8      
Voltage dips and interruptions IEC 61000-4-11      
Generic Immunity Standard for Industrial Environment EN 50082-2
     
         

 