Acuvim-CL-M-5A-P1 Power Meter
รายละเอียดสินค้า
|
About the Acuvim-CL A highly capable but lower cost series of multi-functional single/three phase MODBUS RS485 power meters that measures most common electrical parameters. Available with LCD display or DIN Rail mount transducer (no display). All versions include MODBUS RS485 output.
Acuview Software Features
|
Communication |
RS-485 (Option) |
Modbus-RTU Protocol |
2-wire connection, Half-duplex, Isolated |
1200 to 38400 baud rate |
Current Inputs (Each Channel) | |
Nominal Current | 5 A ac |
Metering Range | 0~6 A ac |
Withstand | 20Arms continuous100Arms for 1 second, non-recurring |
Burden | 0.05VA (typical) @5Arms |
Pickup Current | 10Vac |
Accuracy | 0.50% |
Voltage Inputs (Each Channel) | |
Nominal Full Scale | 400Vac L-N, 690Vac L-L (+20%) |
Withstand | 1500Vac continuous2500Vac, 50/60Hz for 1minute |
Input Impedance | 45Hz~65Hz |
Pickup Voltage | 10Vac |
Accuracy | 0.50% |
Energy Accuracy (Acuvim-EL) | |
Active | (according to IEC 62053-22) Class 0.5s(according to ANSI C12.20) Class 0.5 |
Reactive | (according to IEC 62053-23) Class 2 |
Harmonic Resolution | |
Metered Value | 2nd ~ 15th harmonics(THD of Acuvim-DL is 2nd to 25th) |
Control Power | |
Universal | AC or DC |
AC/DC Control Power | |
Operating Range | 100~415Vac, 50/60Hz, 100~300Vdc |
Burden | 3W |
Withstand | 3250Vac, 50/60Hz for 1 minute |
Low Voltage DC Control Power (Optional) | |
Operating Range | 20~60Vdx |
Burden | 3W |
Digital Output Option | |
Digital Output (DO) | (Photo-MOS) |
Voltage Range | 0~250Vac/dc |
Load Current | 100mA (Max) |
Output Frequency | 25Hz, 50% Duty Ratio |
Isolation Voltage | 2500V |
Digital Input Option | |
Digital Output (DI) | |
Input Voltage Range | 20~250Vac/dc |
Input Current (Max) | 2mA |
Start Voltage | 15V |
Stop Voltage | 5V |
Pulse Frequency (Max) | 100Hz, 50% Duty Ratio |
SOE Resolution | 2ms |
Operating Environment | |
Operation Temperature | -25°C to 70°C |
Storage Temperature | -40°C to 85°C |
Relative Humidity | 5% to 95% non-condensing |
Pollution Degree | 2 |
Standard Compliance | |
Product | |
USA | UL 61010-1 |
Canada | cUL 61010-1 |
Europe | IEC 61010-1 |
Emission | |
Radiated/Conducted | FCC Part 15 Subpart B, Class A |
Radiated/Conducted | EN 55011 |
Harmonic | IEC 61000-3-2 |
Voltage Fluctuation | IEC 50081-2 |
Radio Interference | IEC 50081-2 |
Immunity | |
ESD | IEC 61000-4-2 |
Radiated, radio-frequency, electromagnetic field | IEC 61000-4-3 |
Electrical fast transient/bust | IEC 61000-4-4 |
Surge | IEC 61000-4-5 |
Conducted disturbances | IEC 61000-4-6 |
Power frequency magnetic field | IEC 61000-4-8 |
Voltage dips and interruptions | IEC 61000-4-11 |
Generic Immunity Standard for Industrial Environment | EN 50082-2 |
Specifications | ||||
Metering | ||||
Parameters | Acuvim-L Accuracy | Acuvim-EL/KL Accuracy | Resolution | Range |
Voltage | 0.50% | 0.50% | 0.1V | 20V~1000kV |
Current | 0.50% | 0.50% | 0.001A | 0~50000A |
Current Demand | 0.50% | 0.50% | 0.001A | 0~50000A |
Power | 1.00% | 0.50% | 1W | -9999MW~9999MW |
Reactive Power | 2.00% | 0.50% | 1var | -9999Mvar~9999Mvar |
Apparent Power | 1.00% | 0.50% | 0.001V | 0~9999MVA |
Power Demand | 1.00% | 0.50% | 1W | -9999MW~9999MW |
Reactive Power Demand | 2.00% | 0.50% | 1var | -9999Mvar~9999Mvar |
Apparent Power Demand | 1.00% | 1VA | 1VA | 0~9999MVA |
Power Factor | 1.00% | 0.50% | 0.001 | -1.0~1.0 |
Frequency | 0.20% | 0.20% | 0.01Hz | 45.00~65.00Hz |
Energy | 0.50% | 0.50% | 0.1kWh | 0~99999999.9kWh |
Reactive Energy | 2.00% | 0.50% | 0.1kvarh | 0~99999999.9kvarh |
Apparent Energy | 1.00% | 0.50% | 0.1VAh | 0~99999999.9kVAh |
Harmonics | 2.00% | - | 0.01% | 0~100.0% |
Running Time | 0.1hrs | 0~999999999.9hrs | ||